Single/Three-Phase VFD Input/Output Reactors
The series reactors carry AC current and are essential VFD accessories. Input reactors (commutation reactors) limit commutation voltage drop, suppress harmonics, limit di/dt and du/dt, decouple parallel converters, and protect against voltage surges, switching impulse currents, and radio interference. Output filter reactors compensate for long-cable charging current, limit cable-capacitance-induced motor winding voltage rise, improve output waveform, reduce motor noise, and increase VFD efficiency.
Applicable Power: 0.7 (1.5) – 600 kW
Model Series: OCL-8A – OCL-1400A; ACL-8A – ACL-1400A
Reactance Rate: OCL 1%; ACL 2%
Outline Dimensions: 145 × 135 × 120 – 385 × 245 × 360 mm
Mounting Dimensions: 60 × 59 – 230 × 145 mm
Phase: Single-phase / Three-phase
Application Position: VFD Input Side & Load-Side Output Filtering
Key Features
Motor Noise & Eddy Loss Reduction
Reduces motor noise and eddy current losses.
Input Harmonic Suppression
Suppresses input high-order harmonics.
Smoothing & Motor Life Extension
Provides smoothing and filtering, reduces transient voltage dv/dt, and extends motor service life.
Superior Safety & Stability
The epoxy cast coil absorbs zero moisture and maintains a low partial discharge, allowing for safe operation even in harsh environmental conditions.
VFD Power Device Protection
Protects the internal power switching devices of the VFD.
Technical Parameters
| Applicable Power (kW) | OCL Model | OCL Outline Dimensions (mm) | OCL Mounting Dimensions (mm) | OCL Reactance Rate | ACL Model | ACL Outline Dimensions (mm) | ACL Mounting Dimensions (mm) | ACL Reactance Rate |
|---|---|---|---|---|---|---|---|---|
| 0.7 (1.5) | OCL-8A | 145×135×120 | 60×59 | 1% | ACL-8A | 145×135×120 | 60×59 | 2% |
| 2.2 (4.4) | OCL-10A | 145×135×120 | 60×59 | 1% | ACL-10A | 145×135×120 | 60×59 | 2% |
| 5.5 | OCL-15A | 175×145×145 | 70×67 | 1% | ACL-15A | 175×145×145 | 70×67 | 2% |
| 7.5 | OCL-20A | 175×145×145 | 70×67 | 1% | ACL-20A | 175×145×145 | 70×67 | 2% |
| 11 | OCL-30A | 175×145×145 | 70×67 | 1% | ACL-30A | 175×145×145 | 70×67 | 2% |
| 15 | OCL-40A | 175×145×145 | 70×67 | 1% | ACL-40A | 175×145×145 | 70×67 | 2% |
| 18.5 | OCL-50A | 175×145×145 | 70×67 | 1% | ACL-50A | 175×145×145 | 70×67 | 2% |
| 22 | OCL-60A | 175×145×145 | 70×67 | 1% | ACL-60A | 175×145×145 | 70×67 | 2% |
| 30 | OCL-80A | 205×155×175 | 90×74 | 1% | ACL-80A | 205×155×175 | 90×74 | 2% |
| 37 | OCL-90A | 205×155×175 | 90×74 | 1% | ACL-90A | 205×155×175 | 90×74 | 2% |
| 45 | OCL-120A | 225×160×195 | 110×96 | 1% | ACL-120A | 225×170×195 | 110×106 | 2% |
| 55 | OCL-150A | 225×160×195 | 110×96 | 1% | ACL-150A | 225×170×195 | 110×106 | 2% |
| 75 | OCL-200A | 225×160×215 | 110×96 | 1% | ACL-200A | 225×170×215 | 110×106 | 2% |
| 90 (93) | OCL-250A | 225×175×265 | 120×108 | 1% | ACL-250A | 225×185×265 | 120×118 | 2% |
| 110 | OCL-280A | 225×175×265 | 120×108 | 1% | ACL-280A | 225×185×265 | 120×118 | 2% |
| 132 | OCL-300A | 225×175×265 | 120×108 | 1% | ACL-300A | 225×185×265 | 120×118 | 2% |
| 160 | OCL-400A | 290×200×275 | 133×119 | 1% | ACL-400A | 315×205×285 | 160×118 | 2% |
| 185 (187) | OCL-450A | 290×200×275 | 133×119 | 1% | ACL-450A | 315×205×285 | 160×118 | 2% |
| 200 (220) | OCL-500A | 290×200×275 | 133×119 | 1% | ACL-500A | 315×205×285 | 160×118 | 2% |
| 250 | OCL-600A | 290×200×275 | 133×119 | 1% | ACL-600A | 315×225×285 | 160×138 | 2% |
| 315 | OCL-660A | 315×215×305 | 160×128 | 1% | ACL-660A | 315×225×305 | 160×138 | 2% |
| 375 | OCL-800A | 315×215×305 | 160×128 | 1% | ACL-800A | 315×225×305 | 160×138 | 2% |
| 400 | OCL-1000A | 375×230×360 | 230×145 | 1% | ACL-1000A | 375×230×360 | 230×145 | 2% |
| 500 | OCL-1200A | 385×245×360 | 230×145 | 1% | ACL-1200A | 385×245×360 | 230×145 | 2% |
| 600 | OCL-1400A | 385×240×360 | 230×145 | 1% | ACL-1400A | 385×240×360 | 230×145 | 2% |
Why Choose WeiLian
01 Focused Expertise in Reactive Power Compensation
Weilian focuses on series reactors and reactive power compensation equipment, with deep understanding of power system applications.
02 Quality Control from Material to Finished Product
Strict control over core materials, winding casting, and final testing ensures stable performance and long service life.
03 Application-Driven Customization
Solutions are tailored to harmonic conditions, grid requirements, and project needs—not just standard models.
04 Responsive Service & Long-Term Support
Professional selection support, timely communication, and after-sales service help reduce project risk and O&M costs.